TECHNICAL DATA

Description
HIGH PERFORMANCE RESIDUAL CURRENT DEVICE
Code
BDHP
No. of poles
4P
No. modules
6
Rated current
125 A
Rated residual operating current
300 - 3000 mA
Type
Adjustable
Rated voltage (IEC/EN 60947-2 app. B)
400V
Standard
IEC/EN 60947-2 app. B
Rated frequency (Hz)
50Hz
Insulation voltage
500 V
Rated impulse withstand voltage
4 kV
Overvoltage category
III
Level of immunity (8/20 μs)
3000 A
Section rigid cable
Max 70 mm²
Section flexible cable
Max 50 mm²
Operating temperature
-25 +40 °C
Stocking temperature
-40 +70 °C
Rated tightening torque
3.5 / 3 (terminals)
Adjustable tripping time
0 - 60 - 150 ms
Assembly position
Any
Ware number
85362090

Download

Contact us

Contact our sales representatives to find out all our advantages.

Technical service